Search for the product you are looking for
研发中心

News

Slide down

Life-Cycle Safety Control Points for High-Low Temperature Test Chambers ——A Systematic Implementation Guide from Electrical Earthing to Sample Explosion Protection

Source:LINPIN Time:2025-10-27 Category:Industry News

High-low temperature test chambers reproduce a product’s full-life climatic stress within 72 h by cycling between –70 °C and +180 °C at rates up to 5 °C·min⁻¹. During this process, high-pressure refrigerant, high-speed rotating parts, high-current heaters and potentially explosive samples coexist inside the cabinet. Without proper safety design, electric shock, mechanical injury, fire or even explosion can occur. Based on GB/T 10592, IEC 61010-2-012, ISO 13732-1 and 10 000 chamber-years of aftermarket data, this paper systematically reviews the high-risk points in the four stages of “installation–operation–maintenance–emergency” and provides quantifiable control limits and test methods for laboratory managers, EHS engineers and service providers.

2 Installation Stage—Eliminate Risks Before Power-On
2.1 Protective Earthing and Equipotential Bonding
The resistance between the chamber’s protective-earth terminal and the laboratory earth network shall be ≤ 0.1 Ω (GB/T 16895.3). Use yellow-green Cu wire with a cross-section ≥ 4 mm²; series connection to other equipment is forbidden. If the site uses a TN-C system, create a TN-S arrangement by repeated earthing at the distribution panel to prevent enclosure energisation due to PEN conductor breakage.
2.2 Phase Sequence and Phase-Loss Protection
Incorrect phase sequence causes the three-phase fan to rotate in reverse, reducing airflow by 40 %. Heat cannot be removed from heater surfaces, creating local hot spots. Before energisation, check L1-L2-L3 with a phase-sequence indicator; if only single-phase power is available, install an electronic phase-correction module to avoid manual wiring errors.
2.3 Mechanical Fixation and Levelling
Fix the chamber feet to the floor with M12 expansion bolts; the level shall be ≤ 2 mm·m⁻¹ to prevent resonant displacement when the high-speed fan (2 800 r·min⁻¹) runs. Casters must have dual brakes that automatically lock on slopes ≥ 5° to prevent accidental rolling.
2.4 Flammable-Refrigerant Leak Pre-Assessment
When R404A, R23 or other A1 refrigerants are charged > 2.5 kg per unit, the laboratory shall provide forced ventilation ≥ 12 air changes·h⁻¹ and install an infrared refrigerant detector at 2.5 m above floor with a 1 000 ppm alarm set-point that interlocks the main power supply.
3 Operation Stage—Real-Time Monitoring and Access Control
3.1 Pre-Start Daily Checklist
a) Visually confirm the door seal is not cut and the magnetic gap ≤ 2 mm;
b) Measure heater-to-earth insulation > 50 MΩ (500 V megger);
c) Scan compressor and fan bearings with an IR thermometer; surface temperature rise ≤ 60 K;
d) Verify the emergency-stop button is reset and the PLC shows no alarms.
3.2 Rotating-Part Access Control
Fan-blade tip linear velocity can reach 45 m·s⁻¹, equivalent to the impact energy of a 5 kg mass falling from 0.5 m. Never open the door while running; if the sample rack must be adjusted, first switch off the main power, wait ~30 s for the impeller to stop, then wear cut-resistant gloves.
3.3 Energised-Sample Electrical Isolation
When testing batteries, power resistors or other self-powered devices, use an external supply and install 1 000 V DC feed-through terminals (withstanding 2 500 V·AC for 1 min) at the lead entry to prevent condensed water from tracking along wires and shorting the terminal strip.
3.4 Redundant Over-Temperature Protection
Besides the main PID controller, an independent mechanical thermostat set at set-point +5 °C with 16 A contacts is wired in series with the heater circuit; a 2.0 MPa pressure switch monitors refrigerant high-side pressure—either limit exceeded will cut the heater contactor within 2 s.
4 Maintenance Stage—Eliminate Hidden Dangers on Schedule
4.1 Heater Carbon Deposit Removal
After 500 h at 150 °C, carbonised deposits may form on heater tubes, increasing thermal resistance by 15 % and raising surface temperature, accelerating insulation ageing. Every 6 months wipe with 5 % citric acid, rinse with DI water and re-measure insulation > 50 MΩ.
4.2 Door-Seal Recovery
Silicone door seals exposed to 85 °C/85 %RH for 1 000 h can develop 20 % compression set, doubling air leakage. Soak in 60 °C water for 15 min to restore elasticity; if set exceeds 30 % replace the seal to ensure leakage ≤ 0.05 m³·min⁻¹ (EN 13141-5).
4.3 Refrigerant Leak Detection
Use helium mass-spectrometer leak testing with leak rate ≤ 1×10⁻7 Pa·m³·s⁻¹; if soap-bubble method is used, any bubble > 1 per min at brazed or threaded joints is unacceptable—re-braze and re-pressure-hold for 24 h with pressure drop ≤ 0.05 MPa.
5 Emergency Stage—From Accident Threshold to Personnel Evacuation
5.1 Electric-Shock / Leakage
Hit the emergency stop, remove the victim with an insulated pole, switch off the main supply, start CPR and call 120. Within 24 h test the 30 mA·A type RCD operating time and confirm ≤ 30 ms.
5.2 Major Refrigerant Leak
Start forced exhaust, evacuate personnel to the up-wind side, enter wearing positive-pressure breathing apparatus, close the cylinder valve and use an explosion-proof fan to dilute to < 400 ppm (PEL). 5.3 Sample Explosion When internal pressure spikes, the top bursting disc (2 kPa ±10 %) opens to provide directional relief; if the door seal is blown open, activate a CO₂ extinguisher—never use water to avoid secondary short-circuits. 5.4 Cold / Thermal Burns For −70 °C contact, rewarm with water below 40 °C for 15 min—do not rub; for 150 °C burns, flush with clean cold water for 15 min, cover with sterile dressing and send to hospital. 6 Conclusion The safety threshold of a high-low temperature test chamber is often hidden in the complacency of “three years without an alarm”. Statistics show that 80 % of accidents occur in years 4–5 when maintenance is lacking. Only by closing the five-ring chain of “earthing–interlocking–pressure relief–monitoring–training” can extreme temperatures and high-pressure refrigerants be kept under control, ensuring reliable test data and the safety of personnel and property. All LINPIN chambers are shipped with dual hardware protection, automatic phase-sequence recognition and refrigerant-leak monitoring as standard, together with life-long safety-record hosting services. If a level-3 over-temperature occurs, switch off immediately and call our hotline +86-400-885-6188—we guarantee on-site arrival within 4 h and system recovery within 24 h, safeguarding your extreme-environment testing.

News Recommendation
The thermal shock test chamber is a cornerstone of environmental-reliability testing. Within tens of seconds it transfers specimens between extreme high- and low-temperature zones, revealing mechanical stress, electrical degradation, and chemical instability induced by rapid thermal expansion and contraction.
When purchasing a temperature cycling test chamber, customers must weigh multiple factors, including price, quality, accuracy, and efficiency. Among these, the debate between prioritizing price or quality is particularly common.
Thermal shock test chambers are indispensable in reliability qualification for electronics, aerospace, and automotive industries. Once the “no-cooling” fault occurs, the test sequence is immediately interrupted and secondary damage to the specimen may follow.
There are many important considerations when selecting and using a formaldehyde/VOC environmental test chamber. How many of these are you aware of? Today, we’ll share a few key points—have you noticed them?
After prolonged use of a temperature and humidity test chamber, certain components or systems may develop issues, such as sediment buildup in the water system. To ensure accurate test results, regular cleaning of the water system is essential.
Product Recommendation
Telegram WhatsApp Facebook VK LinkedIn