Search for the product you are looking for
研发中心

News

Slide down

Troubleshooting Guide for Slow Cooling Rate in High-Low Temperature Test Chambers

Source:LINPIN Time:2025-09-06 Category:Industry News

The high-low temperature test chamber is the cornerstone of environmental reliability testing. Its cooling rate dictates test duration and data validity. Field data from 500+ chambers over ten years show that “slow cooling” accounts for 38 % of all malfunctions, second only to “no cooling”. This paper, aligned with GB/T 2423.1 and IEC 60068-3-5, presents a systematic approach to diagnosing and correcting slow-cooling events for laboratories, metrology bodies and manufacturers.
High-Low Temperature Test Chambers
Technical Definition of Cooling Rate
Nominal: empty chamber, +25 °C to –40 °C in ≤ 60 min (JB/T 9512 class A).
Measured: 1 Hz sampling, average of five runs; deviation > +10 % is labelled “slow”.
Boundary conditions: ambient 23 °C ± 2 °C, RH ≤ 65 %, empty, air speed 0.5 m s⁻¹. Any deviation requires correction factor Kθ.
Fault Tree and Weightings
Top-level factors: condenser heat-transfer resistance, ambient coupling, refrigeration circuit, air-side flow, control strategy, load & set-point.
Condenser fouling: 27 % of cases.
Insufficient wall clearance or nearby heat sources: 19 %.
Refrigerant micro-leaks, saturated dryer, expansion-valve drift: 22 %.
Blower speed loss or duct leakage: 15 %.
Conservative PID or faulty defrost logic: 9 %.
Excessive specimen mass or aggressive set-point: 8 %.
Step-by-Step Diagnosis and Quantification
4.1 Condenser Resistance
Measure air-temperature rise ΔT across coil; normal ≤ 8 K, fouled ≥ 12 K.
Measure static-pressure difference ΔP; limit 15 Pa, cleaning required at 30 Pa.
Cleaning: power-off, remove top panel, 0.3 MPa nitrogen blow, 40 °C neutral detergent spray, rinse, 110 °C dry, re-assemble. Expect ≥ 30 % reduction in ΔT.
4.2 Ambient Coupling
Air-cooled units need ≥ 0.6 m from walls, water-cooled ≥ 0.8 m; no ceiling obstruction within 1 m of exhaust.
Ambient range 5–30 °C; every 1 °C above 30 °C lengthens pull-down time by 2.3 %.
Keep ovens or furnaces behind a physical barrier; supply-air temperature must be within 3 K of room air.
4.3 Refrigeration Circuit
R404A at +25 °C ambient: high 1.5 ± 0.1 MPa, low 0.35 ± 0.05 MPa.
High < 1.3 MPa plus low > 0.45 MPa and superheat > 12 K indicate under-charge.
Leak detector sensitivity ≥ 1 g yr⁻¹; annual loss > 1 % requires brazing repair.
Dry-filter temperature difference ≤ 2 K; replace if > 4 K.
Thermal-expansion-valve superheat 6–8 K; electronic valve step-loss < 0.5 %, otherwise replace driver.
4.4 Air-Side Flow
Evaporator face velocity 1.2 ± 0.2 m s⁻¹ (five-point mean).
If < 0.8 m s⁻¹, check blower capacitor, ice or corrosion on impeller, torn flexible duct.
Remedy: change capacitor, rebalance to G 6.3, seal ducts with high-temperature aluminium tape.
4.5 Control Strategy
Defrost initiates when evap. temp. < –25 °C for 40 min; if PID output < 20 % and defrost still triggers, controller misjudges load and reduces speed.
Implement “rate lock-out”: if ΔT/Δt < 0.3 K min⁻¹ for 10 min, defrost is inhibited. PID starting point for empty high-mass chamber: Kp = 1.8, Ki = 0.05, Kd = 0.2; reduce Ki by 30 % when 100 kg aluminium load is present. 4.6 Load & Set-Point Heat load Q = m c ΔT / t. 50 kg steel, c = 0.49 kJ kg⁻¹ K⁻¹, ΔT = 65 K, t = 1 h → Q = 0.44 kW (8.8 % of 5 kW capacity). If Q > 15 %, extend pre-cooling or use step set-points.
Avoid aggressive over-shoot: target –40 °C, do not set –45 °C; instead set –35 °C, wait 10 min, then –40 °C.
Thirty-Minute Field Checklist
Minutes 0–5: verify ambient, wall distance, top exhaust.
Minutes 6–10: read high & low pressure, evap. temp., current.
Minutes 11–20: non-contact ΔT on condenser, velocity grid on evaporator.
Minutes 21–25: inspect filters, capacitor, sight-glass.
Minutes 26–30: log PID output, defrost state, load estimate.
If all values normal yet pull-down > 110 % of nominal, label “hidden system mismatch” and schedule factory calorimeter test.
Maintenance SOP & Intervals
Condenser: daily blow-off, quarterly wash & dry, annual fin-thickness check—replace if < 90 % of original. Dry filter: replace yearly or when ΔP > 0.3 bar.
Blower: visual daily, balance quarterly, grease bearing with 2 g Li-soap grease yearly.
Refrigerant: annual leak test; after recharge run 4 h and analyse acid value < 0.1 mg KOH g⁻¹.
Controller: back-up parameters daily, calibrate sensors quarterly, update firmware and burn-in 72 h yearly.
Closing Remarks
Over ninety per cent of slow-cooling events stem from fouling, ambient issues or minor leaks. Apply the loop “boundary check – quantify – clean/repair – verify” and the chamber usually recovers within two hours. For the remaining ten per cent, factory-level calorimeter testing and model-based re-matching are required. Shift from “fail-and-fix” to “predict-and-prevent” by continuously monitoring discharge pressure, current and condenser ΔT; cloud analytics can issue an alert at a 5 % performance loss, cutting unplanned stops to below one per cent.

News Recommendation
When considering the purchase of a high-temperature test chamber for experiments, you may have concerns about the brand and model specifications.
A UV aging test chamber is composed of many components, each playing an indispensable role. Today, we will introduce some of the common components.
Choosing a high-quality low-temperature test chamber can provide better assurance and save on maintenance costs in the long run. With so many manufacturers of low-temperature test chambers available, how should you correctly select the right model?
Cold and hot shock test chambers are widely used in various industries such as automotive parts, communications, plastics, aerospace, chemical materials, LED, and electronic testing.
The technical indicators of a high-low temperature test chamber have a systematic and multi-dimensional impact on experimental results. The core lies in whether it can accurately simulate the target environmental conditions and maintain controllability throughout the experimental process.
Product Recommendation
Telegram WhatsApp Facebook VK LinkedIn